DC Side Data | ||
Product Model | iCube-C series | |
P-Rate | 0.5P | |
Cell | ||
Cell Type | LFP | |
Cell Capacity | 306Ah | |
Cell Voltage Range | 2.5-3.65V | |
Cell Rated Energy | 979.2Wh | |
System | ||
Configuration | 1P416S | 1P260S |
Rated Energy | 407.34 kWh | 254.59 kWh |
Rated Voltage | 1331.2 VDC | 832 VDC |
Voltage Range | 1040~1500 VDC | 650 ~ 950 VDC |
Rated Charging Current | 153A | 153A |
Maximum Charging Current | 195.8A,<1min | 195.8A,<1min |
Rated Charging Power | 203.67kW | 127.30kW |
Rated Discharging Current | 153A | 153A |
Maximum Discharging Current | 195.8A,<1min | 195.8A,<1min |
Rated Discharging Power | 203.67kW | 127.30kw |
*Table 1: Power and Energy
Auxiliary Power &Communication | ||
Product Model | iCube | |
P-Rate | 0.5P | |
Auxiliary Power1 for BMS | Voltage | L+N+PE/220V/110V±10%, |
Range | 50/60HZ | |
Power | Max.135W | |
Rated Current | 2.3A | |
Inrush | ≤6A,<1S | |
Current | ||
Auxiliary Power2 for coolingunit | Voltage | L+N+PE/220V±20%,50/60HZ |
Range | ||
Power | Max.3kW(Continuous) | |
Rated Current | 10A | |
Inrush | ≤12.5A,<1ms | |
Current | ||
Auxiliary Power3 for Fire FSS | Voltage | 24VDC |
Range | ||
Power | 0.003W(Standby state) | |
27.3W(Alarm status) | ||
Current | 0.125mA(Standby state) | |
1.1375A(Alarm status) | ||
Communication Protocol | CAN, Modbus/TCP |
*Table 2: Electrical Specifications
Mechanical Data | |
Product Model | iCube |
Size | 2348mm(H)*1390mm(W)*1344.1mm(D) |
Weight | 3600±100kg |
IP Level | IP56(Battery Room) |
IP23(Electrical Room) | |
IP66(Control Box) | |
IP66(Battery Modules) | |
IP26(Chiller Unit) | |
Environment condition | |
Charge Temperature Range | -25℃…+55℃ |
Discharge Temperature Range | -25℃…+55℃ |
Storage Temperature Range | -30℃…+60℃ |
Application Altitude | ≤4000m |
Relative Humidity | 0~95%(non-condensing) |
Degree of Anti-corrosion of Battery Unit | C5 |
Seismic Level | IEEE693-2018 Moderate design level |
*Table 3: Mechanical Data and Environmental Specifications